Linkwisetech
Picobox
     
 
CE-T Analog Electrical transducer
Product Range Selection Guide Overview Notice
CE-PJ02,QJ02,PJ31,QJ31,PJ41,QJ41
PRODUCT: Power Analog Transducer
SERIES: CE-PJ02 1 Element Active Power
CE-QJ02 1 Element Reactive Power
CE-PJ31 Active Power (3-Phase 3-Wire)
CE-QJ31 Reactive Power (3-Phase 3-Wire)
CE-PJ41 Active Power (3-Phase 4-Wire)
CE-QJ41 Reactive Power (3-Phase 4-Wire)
INPUT RANGE: 75V*1A~500V*25A
OUTPUT: 5V or 4-20 mA
ACCURACY: 0.5%
RESPONSE TIME: £600 mS
POWER SOURCE: +12V or +15V or +24V
LOAD CAPABILITY: Voltage Output³2kW
Current Output£250W
QUISCENT POWER CONSUMPTION: £960mW
Specifications
CE-PJ02,QJ02,PJ31,QJ31,PJ41,QJ41
CE-PJ02,QJ02,PJ31,QJ31,PJ41,QJ41
CE-PJ02,QJ02,PJ31,QJ31,PJ41,QJ41
Series Operating Principle Isolation Voltage Response Time Range 0 to 90% FS Overload Capacity Quiescent Power(mW) Mounting
Vz,Vd,Vg,Iz Output Iy Output
CE-PJ02
CE-QJ02
Electro-magnetic £2500VDC £900ms Current: 20 Times 5/sec
Voltage: 2 Times 10/sec
300 420 Din rail
CE-PJ31
CE-QJ31
CE-PJ41
CE-QJ41
840 960

 

Series Output Power Source Window
Opening (mm)
Case Style Accuracy Input Range( RMS )
Voltage Current
CE-PJ02
CE-QJ02
CE-PJ31
CE-QJ31
CE-PJ41
CE-QJ41
3---0~5VDC (Vz)
4---0~20mA (Iz)
5---4~20mA (Iy)*
8---0~10V DC(Vd)
2---12V
3---15V
AF4
B-F6.5
S3 0.5 75V, 110V,
220V, 250V,
380V, 400V,
500V
1A, 2A ,
5A, 10A,
15A, 20A,
25A

Part Number Example: CE-PJ41-52BS3-0.5/0~250V*0~5A
Description: Power Transducer, Input Voltage: 0~250V, Current: 0~5A, Output: 4~20mA, Power Source: +12V, Window: F6.5mm, Accuracy: 0.5%, Case style: S3

1 Explain for Code

Code 3 4 5 8
Symbol Vz Iz Iy Vd
Definition DC Voltage Output DC Current Output DC Current Output DC Voltage Output

2 Explain for
* Loop resistance from 0 to 250W. Contact factory for loop resistance above 250 O

Applications
  • Energy Management
  • Motor Efficiency
  • Multi-point power sensing
  • Remote power sensing over long distances
Notice:
  • The input current must pass the window opening in the direction shown in Reference Diagram of Connection.
  • The output signal of 3-phase power transducer corresponds to total power of three phases.
  • For application above 25 Amp use an external current. Connect the secondary leads of the current transformer to the input of the Transducer.
 
     
Privacy Statement